Energy and heating · Battery storage
Container Battery Storage 20C2H500K
Storage system in a 20 foot container with 1.2 MWh of capacity and 500 kW of inverter power. Two grid versions are available: 480 V as 20C2H500K-NA and 400 V as 20C2H500K-EX.
On request
The price depends on quantity, specification and place of delivery.
Description
The cells are lithium iron phosphate at 3.2 V and 280 Ah, wired into six strings in a 1P224S layout. On the DC side this gives a nominal 716.8 V within a range of 602 to 784 V. The inverter delivers 500 kW continuously and 550 kW at peak, with output THDi below 3 percent.
The electrical room and the battery room are separated so that heat from one does not reach the other. Cooling is by HVAC, fire suppression by NOVEC1230 or FM-200. Operation is foreseen from -20 to 40 degrees Celsius and the enclosure is rated IP54. Above 2000 m altitude the output has to be derated, with operation foreseen up to 3000 m.
Technical data
- Battery chemistry
- Lithium iron phosphate (LFP)
- Cell service life
- 80% retention after 5000 cycles at 1C, 25 °C
- Cell data
- 3,2 V / 280 Ah
- String configuration
- 1P224S
- Number of strings
- 6
- Nominal capacity
- 1,2 MWh
- DC rated capacity
- 1,204.224 kWh
- DC nominal voltage
- 716,8 V
- DC voltage range
- 602-784 V
- BMS interface
- RS485, Ethernet
- BMS protocol
- Modbus RTU, Modbus TCP
- AC rated power
- 500 kW
- Maximum AC power
- 550 kW
- AC nominal voltage
- 480 V (20C2H500K-NA) / 400 V (20C2H500K-EX)
- Grid voltage range
- 432-528 V (configurable) / 342-418 V (configurable)
- AC current
- 601,4 A (NA) / 721,7 A (EX)
- Output THDi
- < 3 %
- Power factor
- 0.1 to 1, leading or lagging, controllable
- AC output
- 3-phase 4-wire + PE (NA) / 3-phase + PE (EX)
- Dimensions excluding clearances (L x W x H)
- 6058 x 2438 x 2591 mm
- Total system weight
- 22 t (NA) / 20,7 t (EX)
- Protection rating
- IP54
- Operating temperature range
- -20 to 40 °C
- Relative humidity
- 0 to 95%, non-condensing
- Maximum altitude
- 3000 m, derating above 2000 m
- DC room cooling
- HVAC
- Fire suppression
- NOVEC1230 / FM-200
- Communication interfaces
- RS485, Ethernet, GPRS
- Certificates
- UL9540, IEC62933, UN3536 and others
More from Battery storage.
View all
Energy and heating · Battery storage
Outdoor Cabinet Battery Storage System
An outdoor cabinet holding the battery packs, the PCS power module and the lightning protection module. Air conditioning and fire suppression are part of it; the number and type of battery packs change from project to project.
On request
No image yet
Energy and heating · Battery storage
Energy Management System EMS
- Cell voltage measurement accuracy
- ±5 mV
- Cell voltage sampling interval
- ≤200 ms
- Cell temperature measurement accuracy
- ±2 °C
On request
No image yet
Energy and heating · Battery storage
High Voltage Battery 20-61 kWh
- Capacity
- 20-61 kWh
- Documentation
- UN38.3/MSDS/RoHS
- Series connection
- up to 16 units
On request
No image yet
Energy and heating · Battery storage
High Voltage Battery 48-225 kWh
- Capacity
- 48-225 kWh
- Documentation
- UN38.3/MSDS/RoHS
- Series connection
- up to 16 units
On request